Product Description
The SDM230-LoRaWAN-MID from Eastron Europe is an advanced, multi-function single-phase energy monitoring solution, equipped with a built-in LoRaWAN module. This module enables the device to wirelessly transmit data to any LoRaWAN gateway, making it a versatile tool for remote energy monitoring in single or three-phase networks. The device is designed for a wide array of applications, particularly in settings where wireless communication and accurate energy measurement are crucial.
Key Features
- MID Certification: Ensures compliance with the European Measurement Instruments Directive.
- LoRaWAN EU868: Supports LoRaWAN EU868 frequency band for long-range wireless communication.
- Class 1.0 Accuracy: Provides precise and reliable energy measurements.
- Network Compatibility: Suitable for both single-phase and three-phase networks.
- DIN Rail Mounting: Two-module design, ideal for easy installation on DIN rails.
- Backlit Display: Offers a highly visible and user-friendly interface.
- Pulsed Outputs: Includes one fixed and one configurable pulsed output for various measurement needs.
Displayed Parameters
- Phase to Neutral Voltage (V)
- Phase Current (A)
- Frequency (Hz)
- Power Factor (PF)
- Power Max Demand (MD kW)
- Active Power (kW)
- Reactive Power (kVAr)
- Apparent Power (kVA)
- Import/Export Active Power (kWh)
- Total Active Power (kWh)
- Import/Export Reactive Power (kVAh)
- Total Reactive Power (kVAh)
Product Information
The SDM230-LoRaWAN is engineered with 15 measured parameters and four different kWh measurement modes, tailored to support the development of regeneration projects, such as solar and battery storage systems. The pulsed output of the device can be configured to measure total kWh, nett kWh (Export - Import), Import kWh, or Export kWh, offering flexibility for various energy monitoring scenarios.
Certifications & Standards
- MID: Complies with EN50470-1 & EN50470-3 Class B standards.
- EMC: Meets the requirements of EN61326-1 & EN61326-2-3.
- LVD: Adheres to EN61010-1 & EN61010-2-3 standards.
The SDM230-LoRaWAN-MID is a comprehensive solution for remote energy monitoring, combining high accuracy, ease of use, and wireless connectivity to meet the needs of modern energy management systems.
Product Downloads
General Specifications | |
---|---|
Nominal voltage(Un) | 230V AC |
Operational voltage | 80%~120% of Un |
Insulation capabilities | |
-AC voltage withstand | 4KV for 1 minute |
-Impulse voltage withstand | 6KV~1.2 S |
Basic current(Ib) | 10A |
Maximum rated current(Imax) | 100A |
Operational current range | 0.4% Ib-Imax |
Over current withstand | 30 Imax for 0.01s |
Operational frequency range | 50 or 60Hz |
Internal power consumption | ≤2W/10VA |
Pulse output 1 | 1000imp/kWh(configurable) |
Pulse output 2 | 1000imp/kWh |
Max reading | 99999.99kWh |
Performance | |
Operating humidity | ≤90% |
Storage hunidity | ≤95% |
Operating temperature | -25℃~+55℃ |
Storage temperature | -40℃~+70℃ |
Reference temperature | 23℃±2℃ |
International standard | IEC 62053-21/ EN50470-1/3 |
Accuracy class | Class 1/Class B |
Installation category | CAT II |
Mechanical environment | M1 |
Electromagnetic environment | E2 |
Degree of pollution | 2 |
Protection against penetration of dust and water | IP51(indoor) |
Insulation encased meter of protective class | II |
Electrostatic discharges | 8kV contact / 15kV air gap |
Electromagnetic HF fields | IEC 6100-4-3 |
Electrical fast transients | 4kV |
Surge | 4kV |
Radiated & conducted emissions | EN55022 |
Accuracy | |
Voltage, Current | 0.5% |
Frequency | 0.2% of mid-frequency |
Power factor | 1% of unity(0.01) |
Active power, Apparent power | ±1% of range maximum |
Reactive power | ±1% of range maximum |
Reactive energy(VArh) | Class 2 |
Active energy(Wh) | Class 1 |
Communications | |
Interface standard and protocol | LoRaWAN Specification 1.0.2 |
Frequency | EU868/AS923/AU915/ US902/CN470/CN433 |
LoRaWAN Classes | Class C |
Auto-upload | Max. 20 parameters |
Auto-upload Interval | Configurable |
Activation Way | OTAA or ABP |
Output Power | 13dBm in transmission |
Coding Format | ASCII |
Communication Distance | 1500M in an open area |
Pulse Output | |
Pulse outputs | 2 |
Pulse output type | Passive |
Pulse output 1 | Configurable |
Pulse width | 200 / 100(default) / 60ms |
Pulse output 2 | 1000imp/kWh |
Shipping Policy
We provide worldwide shipping using reliable tracked
shipping services.
Local Shipments within Cyprus
Shipments in Cyprus are performed usually with ACS Courrier
or AKIS Express. In some cases, we might deliver the products ourselves. A pick-up
option from our locations is also available.
International Shipments
International shipments are performed using Express Airway
Shipping Services. We are currently shipping orders with TNT Express and FedEX.
As soon as your shipment is dispatched you will receive the shipment confirmation
including the shipment tracking number which you can use to track your order
from the shipment provider website.
We dispatch orders within 1-3 workdays after the day of the
order placement.
General Return Policy
We have a 30-day return policy, which means you have 30 days
after receiving your item to request a return.
To be eligible for a return, your item must be in the same
condition that you received it, unworn or unused, with tags, and in its
original packaging. You’ll also need the receipt or proof of purchase.
To start a return, you can contact us at sales@cyric.eu. If
your return is accepted, we’ll send you a return shipping label, as well as
instructions on how and where to send your package. Items sent back to us
without first requesting a return will not be accepted.
For any further information, help and support regarding the
shipping and/or return process you can contact us at:
- Email: sales@cyric.eu
- Telephone: +357 22 282828