Black Friday: up to 30% off selected IoT devices until 30 Nov

Half-price shipping to the EU, UK & Switzerland until 6 Dec · Free on most EU orders over €500 (excl. VAT)

Free help & technical advice Contact us

LoRaWAN Energy and Current Monitoring: CT Clamps, DIN-Rail Meters and How to Size a Current Transformer

shopioT blog banner: Energy and current monitoring with LoRaWAN, CT clamps, DIN-rail meters and CT sizing

You can put a building's electricity on a dashboard in two ways. The quick way is a clip-on LoRaWAN current sensor that snaps around a cable and reports amps. The thorough way is a DIN-rail energy meter fed by current transformers, which measures voltage and current together and gives real kWh, power factor and, with an MID meter, numbers you can bill tenants with. Both work over LoRaWAN. Which one you need depends on what decision the data is for, and the CT you pair with it has to be sized properly or the readings will be wrong.

3CT output types: 1 A, 5 A and low-voltage (333 mV or similar)
€14.71starting price for a split-core CT, PowerUC SCT016TS
Class 0.5sMID billing-grade accuracy of the Eastron SDM630MCT
12 circuitsmonitored by one Milesight CTH01 hub
⚡
Who this is forFacility and energy managers, electrical contractors and integrators adding sub-metering to offices, factories, hotels or multi-tenant buildings, without rewiring the distribution board.

Current Sensor or Energy Meter: The Short Answer

Use a clip-on current sensor when you want to know whether a machine is running, how loaded a circuit is, or roughly how consumption changes through the day. Use a CT-operated energy meter when you need real kWh to allocate costs, bill tenants or report to an energy audit. A current sensor measures only current, so any kWh it reports rests on an assumed voltage and power factor. A meter measures both.

Option Measures Install Best for Price
Milesight CT101 (100 A) RMS current, estimated energy Clip around one conductor; powers itself from the cable Single loads: pumps, compressors, HVAC units €75.63
Milesight CT303 / CT305 / CT310 Same, for 300 A, 500 A and 1000 A Clip-on, self-powered Larger feeders and main incomers from €121.01
Dragino CS01 Current on up to 4 probes One node, four detachable probes Machine uptime across several circuits €68.91
Milesight CTH01 12 current + 3 voltage channels: power, energy, PF, harmonics In the panel, with RCT-RJ11 CTs or a Rogowski coil Whole distribution boards, data rooms €360.50
Eastron SDM630MCT + converter 40+ parameters, MID Class 0.5s DIN rail, 1 A or 5 A CTs, Modbus to a UC100 Tenant billing, fiscal sub-metering €81.51 + CTs
Eastron SDM630MCT-LoRa Same meter with LoRaWAN built in DIN rail, CTs, no converter needed Billing-grade metering without Modbus wiring €142.86

Prices excl. VAT, starting price per model, checked October 2026. Some models are on back order; check the product page for stock.

⚠️
Self-powered clamps need current to wake upThe CT101 and CT30x harvest energy from the conductor they measure. On a circuit that's off, or carrying very little load, they can't power themselves and won't report. Check the minimum operating current in the datasheet before fitting one to a standby circuit.

How to Choose a Split-Core Current Transformer

If you go the meter route, the CT is where most mistakes happen. Four things decide it.

1. Output: 1 A, 5 A or low-voltage

A meter expects a specific CT output, and the two must match. The Eastron ESCT-T series comes with a 1 A or 5 A secondary, which suits the SDM630MCT and SDM120CT. 5 A is the traditional industrial standard; 1 A loses less in long secondary cables, so it's the better pick when the CT sits far from the meter. Low-voltage CTs (for example 333 mV) and Rogowski coils produce a small voltage instead of a current and only work with meters built for them, like the CTH01 with its RCT-RJ11 and RRC-RJ11 sensors.

🛡️
Never open a current-output CT under loadA 1 A or 5 A CT with its secondary disconnected can develop a dangerously high voltage. Wire it to the meter, or short its secondary, before clipping it around a live conductor. Installation in a distribution board is work for a qualified electrician.

2. Primary rating

Pick a rated primary current just above the highest current the circuit actually carries. CTs are most accurate near their rated current and less accurate at a small fraction of it, so a 400 A CT on a 40 A circuit gives poor readings at low load. A 63 A breaker usually wants a 60 A to 80 A CT, not a 250 A one "to be safe".

3. Aperture

The window has to fit around the cable, including its insulation, or around the busbar. The PowerUC range has 16, 24, 36 and 45 mm apertures, and the 45 mm SCT045B covers 50 A to 1000 A. Measure the cable before you order; it's the most common reason a CT goes back.

4. Accuracy class

For billing, pair an MID meter with CTs of matching accuracy (Class 0.5 or better). For trend monitoring, Class 1 is fine. The Milesight RCT-RJ11 is Class 0.5 in 100, 300, 500 and 1000 A ranges.

Circuit Typical CT Aperture Pairs with Price
Up to 50 A, small cables PowerUC SCT016TS, 1 A 16 mm SDM120CT, SDM630MCT from €14.71
Up to about 200 A PowerUC SCT024TS, 5 A 24 mm SDM630MCT from €14.71
Mixed sizes, 1 A or 5 A Eastron ESCT-T Several Eastron CT meters from €18.49
Large feeders, 50 to 1000 A PowerUC SCT036TS / SCT045B 36 / 45 mm SDM630MCT from €17.65
Panel hub, 100 to 1000 A Milesight RCT-RJ11 By range CTH01 only from €45.38

Prices excl. VAT, checked October 2026. Confirm the exact rating and aperture on the product page before ordering.

A Typical Set-Up for Tenant Billing

Split-core CTs1 A or 5 A
→
SDM630MCTMID, Class 0.5s
→
UC100 converterModbus to LoRaWAN
→
Gateway + platformbilling, alarms

Three CTs clip around the tenant's phase conductors. The SDM630MCT measures voltage directly and current through the CTs, then the UC100 polls its registers over RS485 and sends kWh over LoRaWAN. One UC100 can read several meters on the same RS485 bus. If you'd rather skip the converter, the SDM630MCT-LoRa has the radio built in. The full approach to cost allocation is in our post on sub-metering for fair tenant billing, and the meter variants are compared in which Eastron SDM630 to buy.

✅
We can pre-configure the CT ratioTell us the CT rating when you order a meter, and we'll set the primary ratio and the converter's polling before it ships, so the first reading on the dashboard is already in the right units.

Frequently Asked Questions

What size current transformer do I need?

Choose a CT whose rated primary current is just above the maximum current of the circuit, with an aperture that fits the cable or busbar, and an output (1 A, 5 A or low-voltage) that matches your meter. For example, a 63 A circuit is usually best served by a 60 A to 80 A CT.

What is the difference between a 1 A and a 5 A CT?

Both produce a current proportional to the primary current; at full rating the secondary carries 1 A or 5 A. 5 A is the older industrial standard. 1 A CTs lose less power in long secondary wiring, so they suit installations where the CT is far from the meter. The meter must be set for the same secondary value.

Can a LoRaWAN current sensor measure kWh?

A clip-on sensor such as the Milesight CT101 measures current and can report estimated energy, but it doesn't measure voltage or power factor. For accurate kWh, use a meter that measures voltage too, such as the Eastron SDM630MCT or the Milesight CTH01.

Do I need to switch off the power to fit a split-core CT?

A split-core CT opens and clips around an existing conductor, so the load does not need to be disconnected. Work inside a distribution board still has to follow local electrical safety rules and should be done by a qualified electrician, and a current-output CT must be connected to its meter before it is clipped on.

Can I bill tenants from LoRaWAN energy data?

Yes, if the readings come from an MID-approved meter such as the Eastron SDM630MCT or SDM630MCT-LoRa. LoRaWAN only carries the meter's register values; it doesn't change them. Clip-on current sensors are fine for monitoring but not for billing.

Decide What the Number Is For

If the data tells you when a machine runs or which circuit is overloaded, a self-powered clamp at €75 does the job. If someone will pay an invoice based on it, use an MID meter with correctly sized CTs. Many sites end up with both: clamps on individual machines and one billing meter per tenant or floor.

Sizing CTs for a Distribution Board?

shopioT is the webstore of CyRIC IoT, an official Eastron and Milesight distributor. Send us a photo of the board and the breaker ratings, and we'll suggest the meter, CTs and converter.

Sources

  • Eastron, Milesight, Dragino and PowerUC product documentation, as summarised on each shopioT product page (October 2026)
  • Directive 2014/32/EU on measuring instruments (MID), Annex V (active electrical energy meters)

Leave a comment